A venue considering a movable partition needs to decide what someone in one room should be able to hear or understand from the other. The acoustician can set a privacy target once the venue describes who will speak and where someone might listen. A panel’s laboratory rating helps compare products. The seals, adjoining construction, and background noise affect what a listener will hear in the finished rooms.
Specify what a person can hear
ASTM E2638 measures sound isolation between a closed room and receiving points outside it, as well as the background noise at those points. John S. Bradley and Bradford N. Gover used measured speech levels from meetings to relate the resulting speech privacy class to the chance that a listener will hear or understand speech. Apply the distinction to a pair of rooms before asking for a number. The client may accept occasional audible voices during a group workshop. An adjoining room used for confidential interviews calls for a criterion tied to whether words can be understood. Identify the closest waiting seat, doorway, or desk that somebody uses on the listening side. ASTM E2638-24, speech privacy, §§1.1 to 1.2 and 5.1 Bradley and Gover, Canadian Acoustics, 2011
ASTM E90 measures airborne sound transmission through a partition specimen in a laboratory. ASTM E336 measures airborne sound attenuation between spaces in a building, where sound can travel through and around the partition. Keep the lab report in the product submittal and put the field criterion in the room specification. Ask the acoustician which field metric and method suit the rooms and intended use. The size and absorption of a room can limit which results the E336 method can report. If the supplier proposes a pass door, ask whether that configuration was part of the laboratory test. ASTM E90-23, laboratory transmission loss, §1.1 ASTM E336-24, field airborne sound attenuation, §§1.1 to 1.4
In his case study of a combined school campus, acoustician Joe Bear reports that the flexible hall and studio partitions had a laboratory rating of 57 dB Rw. The installed pairs measured 26 to 28 dB under the weighted standardized level-difference metric used for those spaces, DnT(Tmf,max),w. Bear converted the field results to an apparent sound reduction index for comparison with the product rating. The case gives the client a reason to reserve time for a site test and any required correction. Keep the quantities and their test conditions with the report so the specification team knows what the result means. Joe Bear, Movable Goalposts, school campus case study, Figures 1 to 3
Follow the routes around the panels
A section through the closed wall should continue to the structure above. Mark a ceiling plenum, a shared duct, and any floor void or perimeter opening that could connect the rooms. The French CERFF guide to demountable partitions diagrams direct and indirect transmission and lists openings for diffusers and open return air as coordination points. Draw each one where it crosses the line between the rooms. Where drawings are issued in separate packages, give the ceiling contractor and partition supplier the same head detail and name the party responsible for closing the space above the track. CERFF, acoustic recommendations for demountable partitions, 2019, section A, in French
The British Columbia Institute of Technology’s design guidance calls for flat, smooth, plumb, and rigid surfaces where movable-wall seals meet the building. Inspect the closing jamb and floor before the supplier comes to set the panels. Where a floor finish changes at the partition line, show the seam in the detail and see whether it leaves the bottom seal a continuous surface. On the receiving side, inspect the adjoining doors and any route through a shared corridor. British Columbia Institute of Technology, Acoustical Guidelines, 2022, Operable Walls
Put the pass door on the same drawing as the room entrance. In one design exercise, a speaker stands near the closed partition while a visitor waits just outside the other room’s corridor door. The sound that reaches the visitor may have taken a different route from the sound heard at a desk against the partition. Ask the acoustician to mark both points. If a report finds a weak result at one point, that drawing tells the contractor where to begin looking for the leak before anyone orders another panel.
Test the way staff will close it
The person who usually operates the partition can close the last panel and engage the seals as they would during ordinary use. Give the staff member a way to tell when it is fully closed. Run the acceptance test with the agreed ventilation setting and record the furnishing and door positions. If a room will operate with quieter ventilation at certain times, ask the acoustician to assess that receiving condition too. Require the report to name the source and listening positions so the test can be repeated after adjustment. Have the operator and acoustician agree which bookings the accepted result supports, including any use that needs a different adjoining room.